Commercial combi boiler combining all the benefits of domestic combi boiler technology while comfortably meeting peak commercial DHW demands.
Space and time saving solution due to not needing to install separate boiler and hot water cylinders.
ErP Class A, NOx levels significantly under 40 mg/kWh and operating efficiencies well above the minimum requirements of Part L (2022) ensure an energy efficient installation.
Internal time clock offers the capability to set up to 6 programmes within a 24 hour period to ensure that fuel usage is managed as efficiently as possible.
Multiple controls options - On/Off, 0-10V power OR temperature control, BMS communication via Modbus.
Corrosion-resistant stainless steel heat exchanger and tank reduces maintenance and increases system lifespan
Suited to high demand and critical hot water premises such as hotels and hospitals
Operates in most efficient mode (condensing) for both heating and hot water
Integrated legionella protection
Supplied with LPG kit for simple on-site conversion
BIM & CAD objects available
Concentric flue gas/air inlet box
Flue gas exhaust tube
Combustion chamber
Stainless steel heat exchanger
Stainless steel “Tank-in-Tank” hot water production tank (primary + DHW)
Primary circuit separation disc
Indirect water pre-heater
Insulation
Condensate recovery dish + NTC5 sensor (flue gas)
High efficiency circulator pump
NTC2 sensor (CH return)
Electrical panel (with spare fuses at the back)
ACVMax Touch Control panel
On-Off switch
DHW tank dry well (Dip tube with temperature sensor)
Automatic air vent
Gas pressure switch
NTC1 sensor (CH supply)
Gas valve
DHW safety valve / (T & P relief valve - UK only)
Modulating air/gas premix burner with fan
Air inlet
Constructive characteristics
HeatMaster 70 Evo 2
HeatMaster 85 Evo 2
HeatMaster 120 Evo 2
Capacity (total)
L
315
315
315
L
Capacity (primary)
L
125
125
125
L
Capacity (domestic hot water)
L
190
190
190
L
Chimney: Max pressure drop in flue pipe
Pa
150
150
170
Pa
Chimney: max length of concentric flue pipe
m
22
22
21
m
Chimney connection
Ømm
100/150
100/150
100/150
Ømm
Connection - heating
Ø"
1 ½ F
1 ½ F
1 ½ F
Ø"
Connection - DHW
Ø"
1 M
1 M
1 M
Ø"
Connection gas
Ø"
3/4 M
3/4 M
3/4 M
Ø"
Connection - re-circulation / safety valve
Ø"
na / 1 F
na / 1 F
na / 1 F
Ø"
Connection - safety valve
Ø"
1/2 M
1/2 M
1/2 M
Ø"
Max operating temperature
°C
87
87
87
°C
Water pressure drop boiler at Δt = 20°C
mbar
9
14
27
mbar
Max service pressure heating (primary)
bar
3
3
3
bar
Max service pressure (DHW)
bar
8,6
8,6
8,6
bar
Pressure drop (primary - ΔT10K)
mbar
9.3
-
-
mbar
Height when tilted
mm
2277
2277
2277
mm
Weight (empty)
kg
298
298
299
kg
Heating characteristics
HeatMaster 70 Evo 2
HeatMaster 85 Evo 2
HeatMaster 120 Evo 2
Pre-heating time from 10 to 80°C (Heat source: boiler)
min
27
24
23
min
Reheat time from 40 to 90°C
min
37
36
30
min
Reheat time from 40 to 80°C
min
18
16
15
min
Heating time from 10 to 90°C
min
47
43
38
min
Combustion
HeatMaster 70 Evo 2
HeatMaster 85 Evo 2
HeatMaster 120 Evo 2
Input max (heating) HCV
kW
77.6
94.4
127.7
kW
Input max (heating) LCV
kW
69.9
85
115
kW
Combustion efficiency
%
98.1
98
97.5
%
Efficiency at 30% load (EN15502-1)
%
109,0
108
108
%
Efficiency at 100% load (50/30°C)
%
105,8
105,8
105,8
%
Efficiency (max output) 80/60°C
%
97,3
97
97
%
Efficiency (min output) 80/60°C
%
97,3
97,5
97,1
%
Efficiency DHW mode ΔT 30K
%
103.9
103.9
102.2
%
CO emissions max output
ppm
34
51
50
ppm
CO emissions min output
ppm
7
6
4
ppm
Mass rate of combustion products (gas)
kg/h
116
143
187
kg/h
NOx weighted (GCV) (EN15502)
mg/kWh
33.1
29.3
39.8
mg/kWh
NOx class (EN15502)
6
6
6
Output power max (80/60°C)
kW
68
82.9
111.7
kW
Output power min (80/60°C)
kW
20.9
20.5
22.9
kW
Output power max (50/30°C)
kW
74
89.9
121.7
kW
Gas flow rate (min output)
m³/h
2.23
2.18
2.40
m³/h
Domestic hot water performance
HeatMaster 70 Evo 2
HeatMaster 85 Evo 2
HeatMaster 120 Evo 2
Peak flow at 40°C
L/10’
716
783
900
L/10’
Peak flow 1st hour at 40°C
L/60’
2455
2895
3620
L/60’
Continuous flow at 40°C
L/h
2087
2534
3402
L/h
Peak flow at 45°C
L/10’
592
646
676
L/10’
Peak flow 1st hour at 45°C
L/60’
2083
2456
3098
L/60’
Continuous flow at 45°C
L/h
1789
2172
2928
L/h
Peak flow at 60°C
L/10’
348
371
440
L/10’
Peak flow 1st hour at 60°C
L/60’
1391
1638
1847
L/60’
Continuous flow at 60°C
L/h
1252
1520
1754
L/h
Electrical Characteristics
HeatMaster 70 Evo 2
HeatMaster 85 Evo 2
HeatMaster 120 Evo 2
Voltage
V
230
230
230
V
Frequency
Hz
50
50
50
Hz
Protection IP
20
20
20
Electrical consumption
W
225
266
352
W
Electrical power requirements
A
1.5
1.9
2.3
A
Eco Design Fields
HeatMaster 70 Evo 2
HeatMaster 85 Evo 2
HeatMaster 120 Evo 2
Space heating energy efficiency class
A
A
A
Seasonal space heating efficiency (35°C)
%
93
92
92
%
Declared load profile
XXL
XXL
XXL
Water heating energy efficiency class
A
A
A
Water heating energy efficiency [ηwh] (EU 814/2013 Art 2 (15) Ann.IV-3)